Clamp-On & Non-Invasive RTD Sensors —No Process Penetration Required

Clamp-on and strap-on RTD sensors measure pipe or tube surface temperature without penetrating the pressure boundary — eliminating the need for isolation valves, hot-tapping, process shutdown, or any modification to the pipe. The sensor is clamped, bolted, or banded to the outside of the pipe and held in firm thermal contact.

No Process PenetrationPipe OD ClampSpring-Loaded ContactPt100 Class A / BMineral-Insulated LeadRetrofit / Temporary / Permanent
Product Series

Clamp-On RTD Configurations

RTD-CO-1

Adjustable Pipe Clamp RTD

A spring-loaded Pt100 element mounted in a stainless steel pipe-clamp body that adjusts to fit pipe OD from 1/2" to 4" NPS. The spring mechanism maintains consistent contact force between the sensing element and the pipe surface across the full temperature range, compensating for thermal expansion. No pipe insulation removal required for standard installation.

1/2" to 4" NPS PipeSpring-Loaded Pt100 Class B3-Wire 316SS Clamp Body
RTD-CO-2

Band-Strap Clamp RTD

A flat Pt100 sensing element bonded to a thermal coupling pad, held against the pipe surface by a stainless steel banding strap. Fits any pipe OD with no adjustment required — the strap wraps and locks. Low profile; compatible with pipe insulation over the top. The lowest-cost non-invasive solution for permanent monitoring installations.

Any Pipe ODSS Banding Strap Pt100 Class B2 or 3-Wire Under Insulation Compatible
RTD-CO-3

Under-Insulation Clamp RTD (UIR)

Designed for permanent installation under pipe insulation, the UIR version uses a low-profile stainless housing and MI-insulated lead cable rated for the high ambient temperature environment under lagging. The Pt100 element is encapsulated in thermally conductive compound within the clamp body to maximise thermal contact with the pipe. Widely used for heat tracing monitoring and steam jacketed piping.

Under InsulationMI Lead Cable Pt100 Class BTo 300°C Heat Trace / Steam Jacket
Specifications
ParameterRTD-CO-1RTD-CO-2RTD-CO-3
ElementPt100 Class BPt100 Class BPt100 Class B
Wire Config3-wire2 or 3-wire3-wire
Pipe Size RangeDN15 to DN100 (½"–4")Any OD — strap adjustableDN20 to DN150
Max Process Temp350°C250°C300°C
Clamp Body316SS machined body316SS banding strap316SS low-profile body
Thermal PadCopper contact padThermally conductive siliconeThermal compound fill
LeadPTFE 3×24 AWG, 36"PTFE 3×24 AWG, 36"MIMS 3-core, 36"
Accuracy Note±2–5°C vs process fluid*±3–8°C vs process fluid*±2–5°C vs process fluid*

* Surface measurement accuracy depends on pipe insulation, flow conditions, and ambient temperature. Not a substitute for immersion measurement where accuracy is critical.

Accuracy Limitation of Surface Measurement

Clamp-on sensors measure pipe outer-surface temperature, not process fluid temperature. In well-insulated, fully-developed turbulent flow, the surface temperature closely tracks the fluid temperature. In low-flow, stratified-flow, or poorly-insulated conditions, a surface measurement may be 5–20°C cooler than the process fluid. For accuracy-critical measurements, use an immersion sensor. For leak detection, heat-trace monitoring, flow confirmation, and safety backup measurements, clamp-on RTDs provide a practical and cost-effective solution.

When to Use Clamp-On RTD

  • Heat tracing verificationRTD-CO-3 under insulation
  • Steam trap monitoringRTD-CO-1 or CO-2
  • Freeze protection alarmRTD-CO-2, any pipe OD
  • Retrofit without shutdownRTD-CO-1 adjustable clamp
  • Temporary commissioningRTD-CO-1 spring-loaded