Duplex & Dual-Element Sensor Assemblies —Measuring + Redundant in One Probe

A duplex sensor houses two independent sensing elements — thermocouple junctions or Pt100 elements — within a single sheath, providing a primary measurement element and a backup in the same probe. When the primary fails, operations switches to the backup without a process shutdown or maintenance intervention to change the probe.

TC + TC DuplexRTD + RTD DuplexTC + RTD CombinationSingle Process NozzleAuto-Failover ReadyRefineries · Power · Aerospace
Configurations

Duplex Assembly Types

ConfigurationElement 1Element 2Primary UseTypical OD
TC/TC DuplexThermocouple (measuring)Thermocouple (redundant)High-criticality process; auto-switch on deviation3/16" to 1/2"
RTD/RTD DuplexPt100 Class A (measuring)Pt100 Class B (backup)Control loop + independent safety trip1/4" to 1/2"
TC/RTD ComboPt100 RTD (accurate control)Thermocouple (OT protection)Control RTD + high-temp overtemp TC in one probe3/8" to 1/2"
Noble Metal DuplexType S (primary calibration)Type S (backup)Furnace control; one element fails without losing controlCeramic tube
Technical Specifications
ParameterTC/TC DuplexRTD/RTD Duplex
Element 1 TypeK, J, N, R, S (specify)Pt100 IEC 60751 Class A
Element 2 TypeSame as Element 1 (std)Pt100 IEC 60751 Class B
Element IsolationElectrically isolated (separate conductors)Electrically isolated — separate MgO columns
Sheath OD3/16" min; 1/4" typical1/4" min; 3/8" typical
Sheath Material316SS or Inconel 600/625316SS or Inconel 600
Process ConnectionNPT, flanged, compressionNPT, flanged, compression
Head TypeDual-compartment or large-bore Form BDual-compartment or DIN-rail head
Wiring4 conductors (2 per element)6 wires (3 per element) standard
CalibrationBoth elements calibrated; matched pairs availableBoth elements calibrated and serialised

Why Duplex in Critical Processes

In a refinery, power plant, or critical manufacturing process, a failed temperature sensor on a key control loop can force an unplanned shutdown that costs tens of thousands of dollars per hour in lost production. A duplex assembly gives the control system an immediate backup without requiring any physical intervention — the backup element is already installed, calibrated, and wired to the system. Switching is either automatic (on deviation alarm) or manual at the DCS operator station.

Head Wiring Options

  • Standard headBoth elements in single terminal block
  • Dual-compartment headSeparate wiring compartments
  • Remote mountElements route to separate panels
  • HART transmitter (RTD/RTD)Dual-input head-mount available