Sanitary RTD Sensors —Tri-Clamp, Hygienic Thread & Flush-Mount

Thermometrics sanitary RTD assemblies are manufactured to 3-A Symbol standards and FDA 21 CFR 177 material requirements for direct contact with food, beverage, pharmaceutical, and biotech process streams. Electropolished 316L SS wetted surfaces, hygienic process connections, and full validation documentation.

3-A Symbol AuthorizedFDA 21 CFR 177Tri-Clamp ½" to 4"Ra ≤ 0.8 µm ElectropolishedCIP / SIP RatedPt100 Class A
Model Series

Sanitary RTD Model Selection

ModelConnection StyleWetted MaterialSealIP RatingApplication
RTD-S10Tri-clamp (½" to 4" ISO 2852)316L SS, Ra ≤ 0.8µm EPEPDM (std) · Silicone · PTFEIP67General dairy, pharma, biotech process
RTD-S11DIN 11851 Hygienic Thread316L SS, Ra ≤ 0.8µm EPEPDMIP67European dairy and food equipment
RTD-S12Varivent® N (GEA-type)316L SS, Ra ≤ 0.8µm EPEPDM or PTFEIP67Tank nozzle, inline vessels
RTD-S20Flush-mount / Van Stone weld-in316L SS, Ra ≤ 0.5µm EPIntegral (no external gasket)IP69KTanks, fermenters, no dead-leg installations
RTD-S30Spring-loaded, tri-clamp body316L SS, Ra ≤ 0.8µm EPEPDMIP67Vessel wall contact, CIP verification points
Specifications

Sanitary RTD Technical Data

ParameterSpecification
Sensing ElementPt100 IEC 60751 Class A (standard) · Class B available
Wire Config3-wire standard; 4-wire for highest accuracy
Wetted Material316L SS — heat number traceable
Surface FinishRa ≤ 0.8 µm electropolished (standard); ≤ 0.5 µm on request
Seals / O-RingsEPDM standard; Silicone; PTFE (FDA-grade)
Temperature Range−50°C to 200°C (standard process)
Pressure RatingTo 150 PSI (10 bar) with standard tri-clamp
CIP CompatibilityRated for NaOH (2%), HNO₃ (1%), peracetic acid CIP agents
SIP CompatibilitySteam sterilization to 135°C / 3 bar
IP RatingIP67 std; IP69K (high-pressure washdown) on request
Head / TransmitterPolycarbonate head (std); DIN-rail transmitter insert available

Validation Documentation Package

  • Material Certificate (316L SS)Heat number traceable
  • Surface Roughness ReportRa, instrument, date
  • Certificate of ConformanceStandard all orders
  • Dimensional Inspection ReportOn request
  • Calibration CertificateNIST-traceable Pt100
  • 3-A Symbol AuthorizationApplicable configurations

No Dead-Leg Design

Dead legs — stagnant pockets in sanitary piping — are a primary concern in CIP system validation. Thermometrics flush-mount and Van Stone weld-in RTDs (RTD-S20) eliminate the pocket volume created by an insertion probe, ensuring complete drainage and CIP solution coverage of all wetted surfaces. Required for USP <1116> and EU GMP Annex 1 compliance in critical pharmaceutical installations.